수냉식 열전 복사 냉방 패널의 냉방 성능 개선을 위한 설계 인자 영향도 분석

An impact analysis of design factor to improve cooling performance of hydraulic thermoelectric radiant panel
  • 김민성
  • 강용권
  • 박효림
  • 김범준
  • 정재원
  • ... 정재원

초록

This study aimed to analyze design factors to improve cooling performance of hydraulic thermoelectric radiantcooling panel (hTERCP) by parametric simulation. The simulation were conducted to examine desirable flow rate andtemperature of cooling water produced by free cooling systems, and to analyze an influence of heat exchange area betweencooling panel and conditioned zone, heat exchange rate and thermal resistance of heat sink. The results showed that thetemperature of cooling water as heat removal factor and heat exchange area between panel and zone have great impacton the cooling performance of the panel. On the other hand, the flow rate of cooling water, and heat exchange rate andthermal resistance of heat sink have relatively less impact on the cooling performance of the panel.

키워드

Thermoelectric technology(열전 기술)radiant cooling panel(복사 냉방 패널)design factor(설계인자)impact analysis(영향도 분석)
제목
수냉식 열전 복사 냉방 패널의 냉방 성능 개선을 위한 설계 인자 영향도 분석
제목 (타언어)
An impact analysis of design factor to improve cooling performance of hydraulic thermoelectric radiant panel
저자
김민성강용권박효림김범준정재원정재원
발행일
2022-11
유형
Proceeding
저널명
대한설비공학회 2022 동계학술발표대회 논문집
페이지
25 ~ 28