증발냉각을 적용한 내부 냉각식 액체식 제습시스템의 실험적 연구

Empirical study of evaporative cooling assisted internally cooled type liquid desiccant system
  • 이성준
  • 임한솔
  • 신장훈
  • 정재원

초록

The purpose of this paper is to evaluate the performance of evaporative cooling assisted internally cooled type liquid desiccant unit. The internally cooled type liquid desiccant (ICLD) consists of two channels: primary air and working air channels. Lithium chloride (LiCl) solution and water are sprayed to process air and working air channels respectively. In the primary air channel, absorption of water vapor from process air is conducted by vapor pressure difference between air and solution. As the water evaporated in the working air channel, the sensible cooling is conducted in the primary air channel. In this paper, air flow rate in the working air channel was considered as a variable to affect the performance of an internally cooled type LD. As the variable was changed, dehumidification efficiency and humidity ratio difference were measured. Humidity ratio difference and dehumidification efficiency,in the case of air flow 350ƋÐîƆ in the working channel, showed better performance compared with others

키워드

제습 시스템내부냉각식 액체식 제습 시스템증발냉각Dehumidification systemInternally cooled liquid desiccant systemevaporative cooling
제목
증발냉각을 적용한 내부 냉각식 액체식 제습시스템의 실험적 연구
제목 (타언어)
Empirical study of evaporative cooling assisted internally cooled type liquid desiccant system
저자
이성준임한솔신장훈정재원
발행일
2016-11
유형
Proceeding
저널명
한국건축친환경설비학회 추계학술발표대회, 2016 (2016-11)
페이지
51 ~ 52