Operating energy savings in a liquid desiccant and dew point evaporative cooling-assisted 100% outdoor air system

Citations

WEB OF SCIENCE

46
Citations

SCOPUS

48

초록

The main purpose of this study is to develop a liquid desiccant and dew point evaporative cooling assisted 100% outdoor air system (LDEOS), and to evaluate its energy saving potentials. In recent years, non-vapor-compression air conditioning systems are becoming available without compromising energy efficiency, thermal comfort, and ventilation requirements. A quasi-dynamic simulation model of LDEOS including a dew point evaporative cooler model was developed to compare the energy performance of LDEOS against a typical variable air volume (VAV) system. A sequence of operation for LDEOS was also proposed. Simulation results showed that LDEOS could save 12% of primary energy compared to a conventional VAV, while 100% of outdoor air was conditioned and delivered to the space without using vapor compression technology. (C) 2016 Elsevier B.V. All rights reserved.

키워드

Non-vapor-compression systemLiquid desiccantDew point evaporative cooling100% outdoor air systemEnergy simulationVENTILATION PRECONDITIONING SYSTEMCONDITIONING SYSTEMDEHUMIDIFICATION SYSTEMHEAT-EXCHANGERSCOUNTER-FLOWPERFORMANCECYCLEREGENERATIONFUNDAMENTALSCONSUMPTION
제목
Operating energy savings in a liquid desiccant and dew point evaporative cooling-assisted 100% outdoor air system
저자
Ham, Sang-WooLee, Sung-JoonJeong, Jae-Weon
DOI
10.1016/j.enbuild.2016.02.011
발행일
2016-03
유형
Article
저널명
Energy and Buildings
116
페이지
535 ~ 552