A heat exchanger with vortex-generating fins at the center of each louver was manufactured. Through 3D computational analysis, we analyzed the air flow characteristics and the fin temperature in the heat exchanger under dry conditions. In addition, we conducted an experiment for observing frost behavior and variation in thermal performance of the louvered fin heat exchanger. The fins generated vortexes and increased the length of air flow, which improved the dry condition thermal performance by 12%. The vortex-generating fins reduced the blockage ratio of frost at the louvers of the head part and improved the frost uniformity of the front and rear sides of the heat exchanger, increasing the usability of the rear louver. Therefore, the decrease in the heat transfer rate of the heat exchanger with vortex generating fins over time by frost formation was smaller than that of the conventional heat exchanger, and the heat transfer performance was improved by at least 28%.

키워드

FrostingHeat exchangerVortex generatorLouvered finTRANSFER ENHANCEMENTDELTA-WINGLETSPUMP SYSTEMSTUBE WALLPERFORMANCEFLOWDESIGNPARAMETERS
제목
Frost behavior of a louvered fin heat exchanger with vortex-generating fins
저자
Park, Jin-SeongByun, SungjoonKim, Dong RipLee, Kwan-Soo
DOI
10.1016/j.ijheatmasstransfer.2017.06.090
발행일
2017-11
유형
Article
저널명
International Journal of Heat and Mass Transfer
114
페이지
590 ~ 596