유기 랭킨 사이클 기반 액체식 제습시스템의 에너지 절감에 대한 실험적 연구

Experimental Assessment of Energy Saving in Liquid Desiccant System with an Organic Rankine Cycle
  • 동혜원
  • 김범준
  • 황유진
  • 임려화
  • 정재원

초록

The main purpose of this study is to evaluate the primary energy saving potential of a liquid desiccant system integrated with an organic Rankine cycle (ORCLD). Based on the previous studies, the experimental apparatus of ORCLD was designed and built. The district heat source of 120°C and Novec649 were utilized as the heat source and the working fluid of ORC. When the maximum power output was achieved based on these conditions, the outlet temperature of the cooling water recovering waste heat from the condenser of ORC was approximately 47°C. The same temperature of water supplied to regenerator was applied to the reference system, which is the LD served by gas fired boiler and existing grid power. As a result, the proposed system could save the 25% of primary energy compared with the reference system. Consequently, the proposed system provides both primary energy savings remaining some of power and heat, which can be used in buildings.

키워드

Organic Rankine cycleLiquid desiccantCombined heat and powerWaste heat recovery유기 랭킨 사이클액체식 제습시스템열병합발전폐열 회수
제목
유기 랭킨 사이클 기반 액체식 제습시스템의 에너지 절감에 대한 실험적 연구
제목 (타언어)
Experimental Assessment of Energy Saving in Liquid Desiccant System with an Organic Rankine Cycle
저자
동혜원김범준황유진임려화정재원
발행일
2020-06
유형
Proceeding
저널명
대한설비공학회 2020 하계학술발표대회 논문집
페이지
604 ~ 607