Experimental study of liquid-desiccant–evaporative cooling for data Center heat recovery

Experimental study of liquid-desiccant-evaporative cooling for data Center heat recovery
Citations

WEB OF SCIENCE

0
Citations

SCOPUS

0

초록

This study presents an experimental evaluation of a rack-level cooling system that integrates rear door heat exchangers with liquid desiccant dehumidification and evaporative cooling to improve thermal efficiency and waste heat utilization in data centers. A test platform simulating a 20 kW server rack was constructed to compare a conventional system with the proposed configuration under humid outdoor conditions. The proposed system recovers approximately 98% of condenser heat, of which about 63% is functionally reused for desiccant regeneration, achieving a total heat recovery utilization rate of 62%. Compared to the baseline, the proposed system reduced cooling-related electricity consumption by up to 29%, primarily due to reduced refrigeration power demand. Results also show lower condensing pressure and compression ratio, leading to improved coefficient of performance and power usage effectiveness. The findings highlight the potential of liquid desiccant-assisted cooling for enhancing energy efficiency and heat reuse in hot and humid climates.

키워드

Data-center coolingLiquid-desiccant dehumidificationPower-usage effectivenessRear-door coolingWaste-heat utilizationWASTE HEATSYSTEMSTRATEGIESMANAGEMENT
제목
Experimental study of liquid-desiccant–evaporative cooling for data Center heat recovery
제목 (타언어)
Experimental study of liquid-desiccant-evaporative cooling for data Center heat recovery
저자
Lee, Soo-JinSim, Jae WooPark, Min-GeonLee, Jae-HeeKim, Dong RipWoo, Je SangKim, Eui JinJeong, Jae-Weon
DOI
10.1016/j.applthermaleng.2026.132064
발행일
2026-08
유형
Article
저널명
Applied Thermal Engineering
302
페이지
1 ~ 15