Seismic performance of intermediate moment frames with RBS-B connections

Citations

SCOPUS

0

초록

The connections of special moment frames (SMF) should have a drift capacity greater than 4%, which is the minimum drift angle required by ANSI/AISC 358-05 for SMF connections. Since some reduced beam section with a bolted web (RBS-B) connection specimens failed to achieve 4% total rotation capacity, RBS-B connection is permitted for use only in Intermediate Moment Frames (IMF) according to the ANSI/AISC 358-05. In previous studies, some RBS-B connections could experience brittle connection fracture during earthquakes, which can also be detrimental to the seismic performance of IMF systems with RBS-B connections. The purpose of this study is to investigate whether IMFs with RBS-B connections provide a satisfactory seismic performance. The seismic performance of IMFs with pre-qualified RBS-B connections is evaluated based on the ATC-63 procedure. It is found that several IMFs with RBS-B connections do not satisfy the acceptance criteria specified in ATC 63.

키워드

Brittle fractureConcrete beams and girdersEngineering geologySeismic wavesSeismologyAcceptance criteriaDrift angleDrift capacityMoment framesReduced beam sectionRotation capacitySeismic PerformanceSpecial moment framesEarthquakes
제목
Seismic performance of intermediate moment frames with RBS-B connections
저자
Han, Sang WhanMoon, Ki-hoonStojadinovic, Bozidar
DOI
10.4231/D3RF5KG33
발행일
2014-07
유형
Conference Paper
저널명
NCEE 2014 - 10th U.S. National Conference on Earthquake Engineering: Frontiers of Earthquake Engineering
페이지
1 ~ 7