중공사막 잠열교환모듈의 여름철 제습 성능 분석에 대한 실험적 연구

Experimental study for dehumidification operation of hollow fiber membrane dehumidifier in summer
  • 조혜진
  • 천성용
  • 이재희
  • 고진영
  • 정재원

초록

This study proposed a hollow fiber membrane dehumidifier, and experimentally investigated the dehumidification and enthalpy exchange performance for the operation in summer. There were four operating parameters of inlet primary air temperature, inlet primary air relative humidity, primary airflow rate, secondary airflow rate, and the dehumidification effectiveness and enthalpy effectiveness were selected as performance indices of a hollow fiber membrane dehumidifier. The measurement results presented that the increase of the inlet primary air temperature and relative humidity have the positive significant effects on dehumidification and enthalpy exchange effectiveness owing to the increase in vapor pressure gradients between primary and secondary airs. In addition, the dehumidification effectiveness and enthalpy effectiveness were significantly increased when the ratio of the primary airflow rate to the secondary airflow rate (airflow rate) increased from 0.67 to 1, while the airflow ratio when varied from 1 to 1.5 showed insignificant effect on the dehumification effectiveness and enthalpy effectiveness.

키워드

Hollow fiber membrane dehumidifierDehumidificationExperiment study중공사막 잠열교환모듈제습실험 연구
제목
중공사막 잠열교환모듈의 여름철 제습 성능 분석에 대한 실험적 연구
제목 (타언어)
Experimental study for dehumidification operation of hollow fiber membrane dehumidifier in summer
저자
조혜진천성용이재희고진영정재원
발행일
2020-11
유형
Proceeding
저널명
대한설비공학회 2020 동계학술발표대회 논문집
페이지
132 ~ 135