상세 보기
시뮬레이션을 이용한 공동주택에서의 플러쉬아웃 효과 평가
- 이기용;
- 김기한;
- 박준석
초록
Studies on the sick building syndrome (SBS) have been carried out actively recently, along with increasing interests in health by improved the public welfare. In order to mitigate the SBS, the Korean government obligates to perform flush-out before the occupancy when newly constructing more than 500 units of multi-family residential buildings in Korea. In this study, we evaluated an effect of flush-out using indoor air quality simulation to figure out how indoor air pollution emissions could be reduced by a performing period, a supply air volume, and indoor temperature and relative humidity during the flush-out. As a result, it revealed that the flush-out should be performed at least 14 days to reduce the indoor air pollution more than a half. In addition, indoor temperature around 20°C and relative humidity around 50% were shown less significant factors affecting indoor air pollution reductions during the flush-out.
키워드
- 제목
- 시뮬레이션을 이용한 공동주택에서의 플러쉬아웃 효과 평가
- 제목 (타언어)
- An Evaluation of Flush-out Effect on Indoor Air Quality in Muti-family Residential Buildings Using Simulation
- 저자
- 이기용; 김기한; 박준석
- 발행일
- 2015-04
- 유형
- Proceeding
- 저널명
- 대한건축학회 춘계학술발표대회논문집
- 권
- 35
- 호
- 1
- 페이지
- 273 ~ 274