공조기를 이용한 가압테스트를 통한 외피 기밀도 실측

Building Envelope leakage measurement using the air-handler fan pressurization approach

초록

This research is a case study performing the air-andler fan pressurization test in a real building. The test has been performed follwing an exiting test method(i.e. CGSB 149.15-96 Standrard). The test building is a 5-story office with a square (32.4m × 32.4m) footprint built in 2001 at Dae-jeon. The test building gas four air-handling units, but the unit located at the basement was out of order. Consequently, the 3 air-handling units installed at the 1st floor and 5th floor were used to pressurize the building. To measure the whole building envelope air leakage, the SA airflow rates in each air handler, operated at the 100% outdoor air mode with closed return and exhaust air dampers, were monitored together with the building pressure. This paper provides some practical information acquired in the field measurement of envelope leakage using the established air-handler fan pressurization test method.

키워드

공조기를 이용한 가압테스트건물 기밀도팬 가압 테스트건물 침기량AHU pressurization testAir-tightnessAir leakage testBuildling Envelope
제목
공조기를 이용한 가압테스트를 통한 외피 기밀도 실측
제목 (타언어)
Building Envelope leakage measurement using the air-handler fan pressurization approach
저자
한슬기조홍재정재원
발행일
2012-10
유형
Proceeding
저널명
한국건축친환경설비학회 2012년도 추계학술발표대회
페이지
109 ~ 112