Energy Saving Potentials of a 100% Outdoor Air System Integrated with Indirect and Direct Evaporative Coolers for Clean Rooms

  • Kim, Min-Hwi
  • Kwon, Oh-Hyun
  • Jin, Jeong-Tak
  • Choi, An-Seop
  • Jeong, Jae-Weon
Citations

WEB OF SCIENCE

5
Citations

SCOPUS

4

초록

In general, HVAC systems for clean room facilities require significant energy to maintain the indoor environment. Due to high air change rates, reducing operating energy consumptions has been a critical issue. The purpose of this paper is to investigate the energy saving potentials of indirect and direct evaporative cooler assisted 100% outdoor air system (IDECOAS) serving a clean room. This research also provides a practical insight on how cooling and heating coil loads can be reduced and how to design the proposed system. In this study, it was assumed that a clean room is served by four different types of HVAC systems: a variable air volume system (VAV), an air washer system (AIRWASH), a dedicated outdoor air system (DOAS), and IDECOAS. It was found that DOAS and IDECOAS can reduce the annual cooling and heating coil loads by over 65.7% and 59.5%, respectively, compared with the VAV.

키워드

clean roomair-washerIDECOASDOASindirect evaporative coolerPOWER-CONSUMPTIONPERFORMANCEMINIENVIRONMENTS
제목
Energy Saving Potentials of a 100% Outdoor Air System Integrated with Indirect and Direct Evaporative Coolers for Clean Rooms
저자
Kim, Min-HwiKwon, Oh-HyunJin, Jeong-TakChoi, An-SeopJeong, Jae-Weon
DOI
10.3130/jaabe.11.399
발행일
2012-11
유형
Article
저널명
Journal of Asian Architecture and Building Engineering
11
2
페이지
399 ~ 405