액체식 제습 시스템의 수조 농도 유지 방안에 따른 수용액 냉각 및 가열 부하 비교

A Comparison on the Cooling and Heating Load for Desiccant Solution by Maintaining the Sump Concentration in a Liquid Desiccant System

초록

The purpose of this study was to compare the cooling and heating loads of liquid desiccant by maintaining the sump concentration in a liquid desiccant system. Case 1 is a liquid desiccant system with a dual sump based on solution exchange. Case 2 is a liquid desiccant system with membrane-based dual sump. Both cases are based on a dual sump, but the technologies used to maintain the concentration of solution in the sump differ. The concentration of the absorber and regenerator sumps in case 2 was similar to that of case 1. The results also indicated that case 2 required 71% lower cooling and heating load for solution than case 1 because the temperature of the absorber sump was lower and the temperature of the regenerator sump was higher. Therefore, case 2 saves energy for solution cooling and heating while maintaining dehumidification and solution regeneration.

키워드

Desiccant solutionCooling loadHeating loadDual sump제습 수용액냉각 부하가열 부하이중 수조
제목
액체식 제습 시스템의 수조 농도 유지 방안에 따른 수용액 냉각 및 가열 부하 비교
제목 (타언어)
A Comparison on the Cooling and Heating Load for Desiccant Solution by Maintaining the Sump Concentration in a Liquid Desiccant System
저자
이수진정재원
DOI
10.6110/KJACR.2020.32.12.558
발행일
2020-12
저널명
설비공학 논문집
32
12
페이지
558 ~ 566

파일 다운로드