액체식 제습 시스템의 수조 농도 유지 방안에 따른 수용액 냉각 및 가열 부하 비교
- 이수진;
- 정재원
초록
The purpose of this study was to compare the cooling and heating loads of liquid desiccant by maintaining the sump concentration in a liquid desiccant system. Case 1 is a liquid desiccant system with a dual sump based on solution exchange. Case 2 is a liquid desiccant system with membrane-based dual sump. Both cases are based on a dual sump, but the technologies used to maintain the concentration of solution in the sump differ. The concentration of the absorber and regenerator sumps in case 2 was similar to that of case 1. The results also indicated that case 2 required 71% lower cooling and heating load for solution than case 1 because the temperature of the absorber sump was lower and the temperature of the regenerator sump was higher. Therefore, case 2 saves energy for solution cooling and heating while maintaining dehumidification and solution regeneration.
키워드
- 제목
- 액체식 제습 시스템의 수조 농도 유지 방안에 따른 수용액 냉각 및 가열 부하 비교
- 제목 (타언어)
- A Comparison on the Cooling and Heating Load for Desiccant Solution by Maintaining the Sump Concentration in a Liquid Desiccant System
- 저자
- 이수진; 정재원
- 발행일
- 2020-12
- 저널명
- 설비공학 논문집
- 권
- 32
- 호
- 12
- 페이지
- 558 ~ 566