Frosting behaviors and thermal performance of louvered fins with unequal louver pitch

Citations

WEB OF SCIENCE

44
Citations

SCOPUS

52

초록

We created heat exchanger louvered fin designs in which the louver pitch successively increased or decreased by 20% from the air inlet region to the redirection region. The frost behavior and thermal performance of the unequal louver pitch design were compared with those of an equal louver pitch design, under both dry and frost conditions. When unequal louver pitch design was used, frost blocking of the spaces between louvers at the front side was delayed and the thermal performance was improved by 21%, compared with the equal louver pitch design. The frost blocking ratios of the two unequal louver pitch designs were compared; the design in which the louver pitch successively decreased from the air inlet region to the redirection region provided more uniform frost growth and improved thermal performance, compared to the design in which the louver pitch successively increased.

키워드

Frost formationScaled-up modelLouvered finUnequal louver pitchMICROCHANNEL HEAT-EXCHANGERSDEFROSTING CHARACTERISTICSDESIGN PARAMETERSPUMP SYSTEMSVELOCITYANGLE
제목
Frosting behaviors and thermal performance of louvered fins with unequal louver pitch
저자
Park, Jin-SeongKim, Dong RipLee, Kwan-Soo
DOI
10.1016/j.ijheatmasstransfer.2015.12.042
발행일
2016-04
유형
Article
저널명
International Journal of Heat and Mass Transfer
95
페이지
499 ~ 505