중공사막 잠열교환소자 적용 환기시스템의 운전 및 에너지 성능에 대한 실험적 연구
- 조혜진;
- 천성용;
- 김범준;
- 이수진;
- 정재원
초록
This study purposed to experimentally investigate the seasonal operating and energy performance of a hollow membrane latent heat exchanger-assisted ventilation unit. The proposed ventilation unit was fabricated, and the experiments was conducted based on the test standards for the energy recovery ventilator addressed from air-conditioning, heating and refrigeration institute (AHRI). In addition, the seasonal operation modes for the proposed ventilation unit were suggested . The measured data showed that the average sensible effectiveness, the average latent effectiveness, and the average enthalpy effectiveness of the proposed ventilation unit are 74.9%, 73.1%, and 76.1% in mode 1; 53.6%, 74.9%, 89.6% in mode 2; 80.6%, 68.1%, 78.1 % in mode 3. In addition, in case of energy performance, the proposed ventilation unit exhibited coefficient of energy (COE) of 31.5 in mode 1, 8.4 in mode 2, and 17.9 in mode 3, which satisfying the minimum requirement addressed in the energy recovery ventilator test standard in Korea.
키워드
- 제목
- 중공사막 잠열교환소자 적용 환기시스템의 운전 및 에너지 성능에 대한 실험적 연구
- 제목 (타언어)
- Experimental analysis on operating and energy performance of hollow fiber membrane-based ventilation unit
- 저자
- 조혜진; 천성용; 김범준; 이수진; 정재원
- 발행일
- 2022-06
- 유형
- Proceeding
- 저널명
- 설비공학 논문집
- 권
- 28
- 호
- 11
- 페이지
- 190 ~ 193