Assessing the applicability of 5th-generation district heating and cooling for energy-efficient retrofits in a net zero energy campus

Citations

WEB OF SCIENCE

0
Citations

SCOPUS

0

초록

This study evaluated the techno-economic and environmental performance of 5th-generation district heating and cooling systems across 13 cases. Key performance indicators included the levelized cost of heat, seasonal coefficient of performance, primary energy consumption, and CO2 emissions. The results showed that the seasonal coefficient of performance values for the 5th-generation district heating and cooling system cases ranged from 4.5 to 4.85, reflecting higher efficiency compared to conventional air-source heat pumps. It leads to the reduction of primary energy consumption and CO2 emissions by up to 45%. Economic performance improved particularly in cases with a larger proportion of data-center cooling load. INT-1 achieved the lowest LCOH of 0.105 $/kWh, which was 9.5% lower than that of the Base case. It also found that the cases with decreased reliance on external heat sources and increased utilization of waste heat recovery also showed lower system capacity requirements and investment costs. This study concluded that load composition optimization and efficient waste heat utilization are key design variables for enhancing the performance and economic viability of 5th-generation district heating and cooling systems.

키워드

5th-generation district heating and coolingEnergy retrofitHeat pumpNet zero energy campusRenewable energySYSTEMS
제목
Assessing the applicability of 5th-generation district heating and cooling for energy-efficient retrofits in a net zero energy campus
저자
Choi, Won-JongLee, WangjeKim, JongkyuJeong, Jae-WeonKim, Min-Hwi
DOI
10.1016/j.enbuild.2026.117771
발행일
2026-09
유형
Article
저널명
Energy and Buildings
367
페이지
1 ~ 17