상세 보기
유기 랭킨 사이클 기반 제습 증발냉각 공조시스템의 1차 에너지 절감효과
- 동혜원 ;
- 박준영;
- 이수진 ;
- 정재원
초록
This research evaluates the impact of an organic Rankine cycle (ORC) powered by various heat sources on enhancing the primary energy saving potential of a liquid desiccant and indirect and direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS). The liquid desiccant used for dehumidification of the process air needs regeneration that in turn requires a low-grade heat, preferably waste heat from a combined heat and power (CHP) system, to maximize the energy benefits in this thermally driven air condition system. Considering that ORC is a promising CHP system, we applied a solar thermal system and a district heat source, respectively, to a 2-kW ORC integrated with an LD-IDECOAS to build two system cases for a comparative study. The primary energy consumption of each system case was estimated and compared using detailed energy simulation. The results of the analyses show that the ORC-integrated LD-IDECOAS powered by the district heat source exhibits the best primary energy saving potential (i.e., 35%).
키워드
- 제목
- 유기 랭킨 사이클 기반 제습 증발냉각 공조시스템의 1차 에너지 절감효과
- 제목 (타언어)
- Primary Energy Savings of a Organic Rankine Cycle in a Liquid Desiccant and Evaporative Cooling-assisted Air Conditioning System
- 저자
- 동혜원 ; 박준영; 이수진 ; 정재원
- 발행일
- 2018-11
- 유형
- Proceeding
- 저널명
- 한국건축친환경설비학회 추계학술발표대회 논문집
- 페이지
- 127 ~ 128