The dielectric recovery characteristics of a molded case circuit breaker (MCCB) are related to re-ignition after current-zero. This characteristic affects the interruption reliability of an MCCB because the fault current cannot be interrupted if re-ignition occurs despite trip unit operation. Therefore, to prevent electric leakage during re-ignition, an improvement in the dielectric recovery characteristic is required. In this paper, the influence of the dielectric recovery characteristics on the splitter plate after current-zero was investigated, and a structure intended to improve the splitter plate was proposed. Measurement of the dielectric recovery voltage confirmed that the proposed structure offered improvement compared with the existing ones.
키워드
- 제목
- Experimental Investigation of Improvement in the Dielectric Recovery Characteristics of a Molded Case Circuit Breaker Splitter Plate
- 저자
- Lee, Kun-A; Ko, Kwang-Cheol
- 발행일
- 2020-03
- 유형
- Article
- 권
- 15
- 호
- 2
- 페이지
- 757 ~ 763