상세 보기
초록
We propose a grid voltage modulated (GVM) direct power control (DPC) strategy for a grid-connected voltage source inverter (VSI) to control the instantaneous active and reactive powers. The GVM-DPC presents the system in d-q frame without using a phase-lock loop. In addition, the GVM method converts the system into a linear time-invariant system. The GVM-DPC is designed to obtain two separate second-order systems for not only the convergence rate of the instantaneous active and reactive powers but also the steady-state performance. In addition, the closed-loop system is exponentially stable in the whole operating range. The proposed method is verified by using MATLAB/Simulink with PLECS blockset. The simulation results show that the proposed method has not only good tracking performances in both active and reactive powers but also a lower current total harmonic distortion than that of the sliding mode control DPC method. Finally, the proposed method is validated by using a hardware-in-the-loop system with a digital signal processor. The experimental results are similar to simulation results. Moreover, the robustness to the line impedance and the grid voltage is tested and discussed.
- 제목
- Grid voltage modulated direct power control for grid connected voltage source inverters
- 저자
- Gui, Y.; Kim, C.; Chung, C.C.
- 발행일
- 2017-05-24
- 학회명
- 2017 American Control Conference, ACC 2017
- 개최지
- Seattle, WA, USA
- 개최국가
- 미국
- 학회 개최일
- 2017-05-24 ~ 2017-05-26