기체 분리막 제습 장치가 적용된 변풍량 공조 시스템의 에너지 성능 분석
- 조혜진;
- 천성용;
- 임려화;
- 정재원
초록
The purpose of this paper is to evaluate energy and operating performance of a vacuum membrane dehumidification (VMD) system-assisted variable air volume (VAV) air conditioning system. The proposed system mainly consists of a vacuum membrane dehumidifier for controlling latent cooling load, and a cooling coil for controlling sensible cooling load. The VMD system dehumidifies the humid process air owing to the pressure difference between the membrane layer. Therefore, the VMD can independently provide latent cooling without the temperature change. The air passing through the VMD is then sensibly cooled by the cooling coil to meet the target supply air condition. To evaluate the energy saving potential of a proposed system, the energy and operating performance in cooling seasons were compared with that of a conventional VAV system via a series of energy simulation using the TRNSYS 18 program and engineering equation solver (EES). The results showed that the latent cooling load from a proposed system was 45% less than that of a reference system, and saved 16% of the primary energy consumption compared with the reference system.
키워드
- 제목
- 기체 분리막 제습 장치가 적용된 변풍량 공조 시스템의 에너지 성능 분석
- 제목 (타언어)
- Energy benefits of a vacuum membrane dehumidification system-assisted variable air volume air-conditioning system
- 저자
- 조혜진; 천성용; 임려화; 정재원
- 발행일
- 2019-11
- 유형
- Proceeding
- 저널명
- 한국건축친환경설비학회 2019 추계학술발표대회 논문집
- 페이지
- 232 ~ 233