다기능 캐스케이드 히트펌프 시스템의 중간 열교환기 설정 온도 변화에 따른 에너지 성능 분석

Energy performance analysis of a multi-functional cascade heat pump system based on set-temperature variation of intermediate heat exchanger
  • 김범준
  • 조혜진
  • 조수영
  • 김세헌
  • 정재원

초록

This study conducted determining the range of the intermediate heat exchanger temperature value of the multi-functional cascade heat pump system according to the design conditions of the residential building. In addition, the system performance and energy consumption according to the intermediate temperature change were analyzed. A residential building was set to 100m2 area. The thermal load of building was calculated by TRNSYS program. The thermodynamic equation and the EnergyPlus model equation were used for system analysis. The result showed that the optimal temperature range of the intermediate heat exchanger was 55℃~61℃ by various building design constraint. Since the energy consumption of the low-cycle compressor was dominant, the proposed system should be set to indoor unit conditions.

키워드

Cascade heat pump(캐스케이드 히트펌프)Multi-functional system(다기능 시스템)Intermediate heat exchanger(중간열교환기)Residential building(주거용 건물)Building energy-saving(건물에너지 절감)
제목
다기능 캐스케이드 히트펌프 시스템의 중간 열교환기 설정 온도 변화에 따른 에너지 성능 분석
제목 (타언어)
Energy performance analysis of a multi-functional cascade heat pump system based on set-temperature variation of intermediate heat exchanger
저자
김범준조혜진조수영김세헌정재원
발행일
2022-11
유형
Proceeding
저널명
대한설비공학회 2022 동계학술발표대회 논문집
페이지
60 ~ 63