상세 보기
System design and performance assessment of hollow fiber membrane-based humidifier for HVAC applications
- Cho, Hye-Jin;
- Cheon, Seong-Yong;
- Park, Sang-Hwan;
- Jeong, Jae-Weon
WEB OF SCIENCE
3SCOPUS
5초록
Recently, hollow-fiber membrane technology has emerged as a clean and energy-efficient humidification system for air-conditioning, utilizing indirect air–water contact. This study proposed a water-to-air cross-flow hollow fiber membrane module, featuring cylindrical shell-and-tube bundles in a rectangular block, as an air humidifier for air-conditioning systems. Two-dimensional heat and mass transfer equations governing water-to-air interactions were numerically solved. Key operating parameters, including inlet water temperature and water flow ratio, and a design parameter, the number of mass transfer units of the membrane (NTUm), were analyzed. A parametric study was conducted to evaluate the effects of these factors on humidifier performance. The simulation results demonstrated that the inlet water temperature (1–48.4 °C) and NTUm (0.15–2.35) ranges required to achieve the target air humidity ratio (0.008–0.011 kg/kg). Furthermore, to achieve performance comparable to isothermal humidification, it is recommended to operate the humidifier with a water temperature in the range of 35.5 –47 °C and NTUm between 0.15 and 0.45.
키워드
- 제목
- System design and performance assessment of hollow fiber membrane-based humidifier for HVAC applications
- 저자
- Cho, Hye-Jin; Cheon, Seong-Yong; Park, Sang-Hwan; Jeong, Jae-Weon
- 발행일
- 2025-04
- 유형
- Article
- 권
- 265
- 페이지
- 1 ~ 17