상세 보기
Heat pump를 적용한 액체식 제습 시스템의 겨울철 가습 운전에 대한 실험적 연구
- 임한솔;
- 이수진;
- 동혜원;
- 조혜진;
- 정재원
초록
The performance of regenerator in heat pump integrated liquid desiccant (LD) system was investigated for the operation in winter. The performance parameters for regenerator were the regeneration effectiveness and enthalpy exchange effectiveness. There were five independent parameters of inlet air temperature, inlet air humidity ratio, inlet solution temperature, concentration of solution and liquid-to-gas ratio. The experimental model was constructed using an adiabatic cross flow regenerator with lithium chloride solution. Based on 2k and 3k factorial design method, total 48 experiment sets were designed to develop prediction models for two performance parameters. The results showed that the solution temperature and liquit-to-gas ratio have significant effects on the regeneration effectiveness and enthalpy exchange effectiveness of regenerator. In addition, the amount of humidification was ranged from 3.23 g/㎏a to 51.18 g/㎏a, therefore it was enough for humidification system in winter.
키워드
- 제목
- Heat pump를 적용한 액체식 제습 시스템의 겨울철 가습 운전에 대한 실험적 연구
- 제목 (타언어)
- Experimental study for humidification operation of heat pump integrated liquid desiccant system in winter
- 저자
- 임한솔; 이수진; 동혜원; 조혜진; 정재원
- 발행일
- 2019-11
- 유형
- Proceeding
- 저널명
- 대한설비공학회 2019 동계학술발표대회 논문집
- 페이지
- 261 ~ 264