공동주택 중앙 환기 시스템 적용을 위한 유기랭킨사이클 기반 제습증발냉각 환기 시스템의 에너지 성능 평가

Energy Performance of liquid desiccant dehumidification and Evaporative Cooling Ventilation System with Organic Rankine Cycle for Central Ventilation System of Apartments
  • 김범준
  • 동혜원
  • 이재희
  • 정재원

초록

This paper was proposed a liquid desiccant assisted-dedicated outdoor air system with organic Rankine cycle. The energy performance of the proposed system was determined as a central ventilation system of a high-rise apartment building. A dedicated outdoor air system using desiccant wheel was considered as a compared system. The waste heat released from the organic Rankine cycle was used for regeneration heat in the proposed system. The thermal load of the 30-stories apartment building model was calculated by TRNSYS 18 program. The result showed that the proposed system saved 71.4% of the primary energy than the reference system because of the recovering of the waste heat from the organic Rankine cycle.

키워드

공동주택중앙환기유기랭킨사이클외기전담시스템액체식 제습시스템Apartment buildingCentral ventilationOrganic Rankine cycleDedicated outdoor air systemLiquid desiccant system
제목
공동주택 중앙 환기 시스템 적용을 위한 유기랭킨사이클 기반 제습증발냉각 환기 시스템의 에너지 성능 평가
제목 (타언어)
Energy Performance of liquid desiccant dehumidification and Evaporative Cooling Ventilation System with Organic Rankine Cycle for Central Ventilation System of Apartments
저자
김범준동혜원이재희정재원
발행일
2019-11
유형
Proceeding
저널명
한국건축친환경설비학회 2019 추계학술발표대회 논문집
페이지
83 ~ 84