이중 변환 UPS의 병렬 운전 시 외란 저감 성능 향상을 위한 정지 좌표계 상의 전향 보상 기법
- 류효준;
- 윤영두;
- 모재성;
- 최승철;
- 우태겸
초록
Generally, a proportional-resonant controller is used to eliminate steady-state errors during the voltage–current control of a double-conversion uninterruptible power supply (UPS) in a stationary reference frame.Additionally, the feed-forward control compensating for the load current, which can be considered a disturbanceof the voltage controller, can be used to improve the disturbance rejection performance. However, during theparallel operation of UPSs, circulating current can occur between UPS modules when performing bothfeed-forward control and droop control because feed-forward control reduces the circulating current impedance.This study proposes a feed-forward compensation technique that considers the impedance of circulating current.An additional feed-forward compensation technique is developed to enhance the disturbance rejectionperformance. The validity of the proposed feed-forward compensation technique is verified by the experiment results of the parallel operation of a 500 W double-conversion UPS module.
키워드
- 제목
- 이중 변환 UPS의 병렬 운전 시 외란 저감 성능 향상을 위한 정지 좌표계 상의 전향 보상 기법
- 제목 (타언어)
- Feed-Forward Compensation Technique in Stationary Reference Frame for the Enhanced Disturbance Rejection Performance in Parallel Operation of Double-Conversion UPS
- 저자
- 류효준; 윤영두; 모재성; 최승철; 우태겸
- 발행일
- 2021-11
- 유형
- Proceeding
- 저널명
- 전력전자학회 2021년도 추계학술대회 논문집
- 페이지
- 1 ~ 3