상세 보기
전열교환 환기장치의 효율을 고려한 결로 방지용 예열 온도 예측 모델 개발
Development of Pre-heat Temperature Prediction Model for Condensation Prevention regarding Effectiveness of Energy Recovery
Ventilator
- 고진영;
- 정재원
초록
Although Korean government tried to enact the law about mandatory pre-heat coil installation in Energy Recovery Ventilator(ERV), the plan was withdrawn due to the concern about excessive energy consumption. Therefore, the other alternative concerning real-time climate difference and effectiveness difference about the pre-heater regulation has been required to prevent the condensation problem. This study suggests a real-time control criterion applying the frost threshold temperature. With the new control measure, not only the energy consumption of pre-heat coil decreased by 61% from the previous suggested method, but also 31% less coil capacity was needed for operation in order to preclude the condensation problem.
키워드
전열교환 환기장치; 결로; 결빙; 예열코일; Energy Recovery Ventilator; Condensation; Frost; Pre-heat Coil
- 제목
- 전열교환 환기장치의 효율을 고려한 결로 방지용 예열 온도 예측 모델 개발
- 제목 (타언어)
- Development of Pre-heat Temperature Prediction Model for Condensation Prevention regarding Effectiveness of Energy Recovery Ventilator
- 저자
- 고진영; 정재원
- 발행일
- 2019-11
- 유형
- Proceeding
- 저널명
- 한국생태환경건축학회 2019년도 추계국제학술발표대회 논문집
- 권
- 19
- 호
- 2
- 페이지
- 140 ~ 141