현열 및 잠열교환 효율 차이를 고려한 전열교환 환기장치의 결로방지용 예열코일 용량산정에 관한 연구

Determination of Preheat Coil Capacity in an Energy Recovery Ventilator Considering the Differences in Sensible and latent Effectiveness Values

초록

Energy recovery ventilator (ERV) is designed to improve the indoor air quality and reduce the heating/cooling load during the ventilation. However, condensation/frosting could occur at energy exchange element in winter season. Condensation/frost problems could reduce the effectiveness of ERV and harmful to occupant. To prevent the condensation/frosting, outdoor air should be preheated over the frost threshold temperature. In this study, the process of condensation/frosting in ERV could confirm, and preheat coil capacity was calculated under various indoor air conditions, outdoor air conditions, and sensible/latent effectiveness of ERV to prevent the condensation/frost. Control strategies of preheat coil were modeled using the temperature of exhaust air and dew point temperature. Annual preheating coil loads were calculated by Korea region. It was found that the preheat coil capacity of seoul was calculated about 200 W, and the maximum capacity of preheat coil region was chuncheon, which has 277 W

키워드

Energy recovery ventilatorSensible effectivenessLatent effectivenessCondensationFrost전열교환 환기장치현열교환 효율잠열교환 효율결로결빙
제목
현열 및 잠열교환 효율 차이를 고려한 전열교환 환기장치의 결로방지용 예열코일 용량산정에 관한 연구
제목 (타언어)
Determination of Preheat Coil Capacity in an Energy Recovery Ventilator Considering the Differences in Sensible and latent Effectiveness Values
저자
김원준정재원
발행일
2017-06
저널명
한국건축친환경설비학회 논문집
11
3
페이지
197 ~ 202