Energy benefit of a cascade liquid desiccant dehumidification in a desiccant and evaporative cooling-assisted building air-conditioning system

Citations

WEB OF SCIENCE

28
Citations

SCOPUS

29

초록

The main objective of this study was to estimate the impact of dehumidification with a cascade liquid desiccant on the primary energy consumption in a liquid desiccant and evaporative cooling-assisted 100% outdoor air system. Detailed energy simulations were performed for two systems serving an identical office space: the conventional liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) (i.e., Case 1) having a single-stage liquid desiccant dehumidification section, and a retrofit case of the LD-IDECOAS having a cascade liquid desiccant section (i.e., Case 2) consisting of a two-stage liquid desiccant dehumidifier. The results showed that Case 2 consumed 12% less primary energy under the peak load condition and 17.4% less primary energy during the cooling season. The overall thermal and primary coefficients of performance of Case 2 were 0.78 and 2.05, respectively, whereas those of Case 1 were 0.65 and 1.45, respectively. In addition, it was also observed that Case 2 could provide lower supply air temperature to the conditioned space compared with Case 1 owing to enhanced evaporative cooling performance, which was mainly caused by enhanced dehumidification in the cascade liquid desiccant section. The lower supply air temperature resulted in reductions in fan and pump energy consumptions during the operation.

키워드

Liquid desiccant systemEvaporative cooling system100% outdoor air systemPERFORMANCE
제목
Energy benefit of a cascade liquid desiccant dehumidification in a desiccant and evaporative cooling-assisted building air-conditioning system
저자
Park, Joon-YoungDong, Hye-WonCho, Hye-JinJeong, Jae-Weon
DOI
10.1016/j.applthermaleng.2018.10.101
발행일
2019-01
유형
Article
저널명
Applied Thermal Engineering
147
페이지
291 ~ 301