상세 보기
Noise reduction of refrigerant two-phase flow using flow conditioners near the electric expansion valve
- Kim, Gangjune;
- Song, Simon
WEB OF SCIENCE
23SCOPUS
29초록
Two-phase flow, particularly generated in an expansion device, is a primary cause of refrigerant-induced noise in an air-conditioning system. The indoor unit (IDU) of a multi-split air source heat pump (ASHP) for both heating and cooling must include an electric expansion valve (EEV); therefore, consumers have perceived the increased noise. To reduce this noise, we experimentally investigated the two-phase flow and consequent noise by applying a honeycomb and porous metal as a flow conditioner to the EEV in the IDU of a multi-split ASHP. Flow conditioning near the EEV with the honeycomb and porous metal made the two-phase flow steadier and more uniform, leading to reduced noise and frequency variation for the three heat operation modes of a multi-split ASHP. The noise reduction was also verified in the transient operating modes of a real IDU.
키워드
- 제목
- Noise reduction of refrigerant two-phase flow using flow conditioners near the electric expansion valve
- 저자
- Kim, Gangjune; Song, Simon
- 발행일
- 2020-02
- 유형
- Article
- 권
- 34
- 호
- 2
- 페이지
- 719 ~ 725
- 언어
- ENG
- 출판사
- KOREAN SOC MECHANICAL ENGINEERS
- 발행국가
- 대한민국
- 분량
- 7 페이지
- ISSN
- E 1976-3824
P 1738-494X