Numerical and Experimental Study on the Performance of Thermoelectric Radiant Panel for Space Heating

Citations

WEB OF SCIENCE

8
Citations

SCOPUS

7

초록

The purpose of this study is to investigate the suitable operation and performance of a thermoelectric radiant panel (TERP) in the heating operation. First, the hypothesis was suggested that the heating operation of TERP can operate without a heat source at the cold side according to theoretical considerations. To prove this hypothesis, the thermal behavior of the TERP was investigated during the heating operation using a numerical simulation based on the finite difference method. The results indicated that it is possible to heat the radiant panel using a thermoelectric module without fan operation via the Joule effect. A mockup model of the TERP was constructed, and the numerical model and hypothesis were validated in experiment 1. Moreover, experiment 2 was performed to evaluate the necessity of fan operation in the heating operation of TERP regarding energy consumption. The results revealed that the TERP without fan operation showed the higher coefficient of performance (COP) in the heating season. After determining the suitable heating operation of the TERP, prediction models for the heating capacity and power consumption of the TERP were developed using the response surface methodology. Both models exhibited good R-2 values of >0.94 and were validated within 10% error bounds in experimental cases. These prediction models are expected to be utilized in whole-building simulation programs for estimating the energy consumption of TERPs in the heating mode.

키워드

Radiant heatingthermoelectric moduleempirical modelingfinite difference methodnon-vapor compressionSYSTEMTECHNOLOGYCONVECTIONDESIGNUNITWALL
제목
Numerical and Experimental Study on the Performance of Thermoelectric Radiant Panel for Space Heating
저자
Lim, HansolJeong, Jae Weon
DOI
10.3390/ma13030550
발행일
2020-02
유형
Article
저널명
Materials
13
3
페이지
1 ~ 19

파일 다운로드