외기전담 시스템과 고성능 제습-증발냉각 시스템의 성능 비교 연구

Performance Comparison of the Dedicated Outdoor Air System and Desiccant-enhanced Evaporative Cooling system

초록

The main purpose of this paper is to analyze the characteristics and the performances of dedicated outdoor air system (DOAS) and desiccant-enhanced evaporative air conditioner (DEVap). The systems take two different air handling strategies. DOAS, mainly used for enhancing indoor air quality and humidity rate, is compromised of constant flow air handling unit and additional parallel cooling system. On the other hand, DEVap takes advantages of liquid desiccant system and regenerative indirect evaporative cooler with variable air flow rate. Although DOAS and DEVap are different in terms of their system compositions and the mode of operations, performance comparison of the systems is necessary to investigate more effective and energy conservative system. The primary energy as well as cooling and dehumidification capacities of two systems during summer season are analyzed through computer simulation with a commercial equation solver and a TRNSYS 17 program. As a result, DOAS conserved up to 61% of the primary energy and showed better cooling and dehumidification performance than DEVap.

키워드

외기전담 시스템병렬냉방시스템고성능 제습-증발 냉각 공조 시스템정풍량 공조시스템변풍량 공조시스템Dedicated outdoor air system (DOAS)Parallel cooling systemDesiccant enhanced evaporative air conditionerconstant air volume systemvariable air volume system
제목
외기전담 시스템과 고성능 제습-증발냉각 시스템의 성능 비교 연구
제목 (타언어)
Performance Comparison of the Dedicated Outdoor Air System and Desiccant-enhanced Evaporative Cooling system
저자
김희정윤동섭정재원
발행일
2015-10
유형
Proceeding
저널명
대한건축학회 창립70주년기념대회 및 추계학술발표대회논문집
35
2
페이지
279 ~ 280