유기랭킨사이클을 결합한 제습증발냉각 기반 공동주택 중앙 환기 시스템의 에너지 성능 분석

Energy Performance Analysis of Liquid Desiccant Assisted-Dedicated Outdoor Air System with Organic Rankine Cycle to an Apartment Central Ventilation System

초록

A liquid desiccant-assisted dedicated outdoor air system (LDADOAS) with organic Rankine cycle (ORC) was proposed as a centralized ventilation system applicable to high-rise apartment buildings. The LDADOAS consists of a liquid desiccant dehumidifier and an indirect evaporative cooler for conditioning the minimum required outdoor air ventilation. The ORC considered in this research is a combined heat and power system to accommodate common electricity demand of the apartment building. The heat released from the ORC is used for regeneration of the desiccant solution in the proposed system. Energy performance of the proposed system was compared with existing dedicated outdoor air systems via detailed energy simulation. The result showed that the LDADOAS consumed 48% less primary energy consumption compared with conventional dedicated outdoor air system considered in this work because most of regeneration heat required for the proposed system was supplied by the waste heat recovered from the ORC.

키워드

유기랭킨사이클액체식 제습 시스템외기전담 시스템중앙 환기공동주택Organic Rankine cycleLiquid desiccant systemCentral ventilation systemDedicated outdoor air systemApartment building
제목
유기랭킨사이클을 결합한 제습증발냉각 기반 공동주택 중앙 환기 시스템의 에너지 성능 분석
제목 (타언어)
Energy Performance Analysis of Liquid Desiccant Assisted-Dedicated Outdoor Air System with Organic Rankine Cycle to an Apartment Central Ventilation System
저자
김범준동혜원정재원
DOI
10.22696/jkiaebs.20190034
발행일
2019-10
저널명
한국건축친환경설비학회 논문집
13
5
페이지
394 ~ 402

파일 다운로드