액체식 제습 시스템의 겨울철 가습 운전에 의한 에너지 절감 효과 분석

Energy Benefits of Liquid Desiccant System for Humidification in Winter
  • 이수진
  • 임한솔
  • 조혜진
  • 천성용
  • 정재원

초록

This study aimed to evaluate the energy benefits of liquid desiccant system for humidification in winter based on the regenerator process compared with direct-injection steam humidifier. The heat pump was selected as a heat source of liquid desiccant system because the heat pump can be operated for both cooling and heating by reverse cycle. The regeneration effectiveness and enthalpy effectiveness were used to estimate conditions of the process air leaving a regenerator of the liquid desiccant system. The results showed that the proposed system could save 42% primary energy consumption compared the reference system with direct-injection steam humidifier in winter. The liquid desiccant system for humidification needed low grade heat source while steam humidifier required high temperature heat source to provide the steam. The pre-heating the process air through regenerator in the proposed system is also critical to reduction in the operating energy.

키워드

Liquid desiccant systemHumidificationRegeneratorDirect-injection steam humidifier액체식 제습 시스템가습재생기스팀 분사형 가습기
제목
액체식 제습 시스템의 겨울철 가습 운전에 의한 에너지 절감 효과 분석
제목 (타언어)
Energy Benefits of Liquid Desiccant System for Humidification in Winter
저자
이수진임한솔조혜진천성용정재원
발행일
2020-06
유형
Proceeding
저널명
대한설비공학회 2020 하계학술발표대회 논문집
페이지
883 ~ 886