식물공장을 위한 연료전지가 적용된 제습공조시스템의 에너지 절감효과 분석

Energy Saving Potential of Desiccant-Assisted Air Conditioning System Integrated with PEMFC for Smart Farm
  • 임려화
  • 동혜원
  • 강용권
  • 황유진
  • 정재원

초록

This paper aimed to analyze the annual energy consumption of the heat pump-driven liquid desiccant (HPLD) system combined with a fuel cell in the plant factory. Through simulation, it is found that in a plant factory with an area of 200 square meters, the HPLD air conditioning system only needs 48.12MWh of fuel and 25.66MWh of electricity for operation throughout the year. The proton exchange membrane fuel cell (PEMFC) selected in this study can meet 79.9% of the electricity and 76.4% of the heat demand of this plant factory. At the same time, fuel cell by-products (i.e., water and carbon dioxide) can be supplied to plants. It can meet 7.2% of the daily water demand of plants and reduce 18.5% of carbon dioxide emissions.

키워드

Liquid desiccantPlant factoryPEMFCCarbon dioxide액체식 제습제식물공장이산화탄소
제목
식물공장을 위한 연료전지가 적용된 제습공조시스템의 에너지 절감효과 분석
제목 (타언어)
Energy Saving Potential of Desiccant-Assisted Air Conditioning System Integrated with PEMFC for Smart Farm
저자
임려화동혜원강용권황유진정재원
발행일
2020-11
유형
Proceeding
저널명
대한설비공학회 2020 동계학술발표대회 논문집
페이지
55 ~ 58