컨테인먼트가 적용된 모듈러 데이터센터의 공조 팬 제어 방안에 관한 실험적 연구

An experimental study on the fan control of computer room air handler in a modular data center with cold-aisle containment
  • 함상우
  • 김민휘
  • 윤동섭
  • 정재원

초록

The purpose of this study is to experimentally demonstrate the fan control strategy of computer room air handler (CRAH) in amodular data center with containment architecture. In containment architecture, variable speed drive fan is widely accepted in orderto reduce fan energy. However, the selection of inappropriate control variable for fan speed yields improper operation of fan; fanairflow does not change when the IT equipment is in part-load operation. In this study, fan control strategy that modulates fanspeed according to the differential pressure between cold- and hot-aisle through containment is experimented. As a result, thisstrategy reduces the discrepancy between rack and CRAH fan airflow though small recirculation is occurred due to gap betweenfloor and racks.

키워드

모듈러 데이터센터공조 팬 제어컨테인먼트Modular Data CenterCRAH Fan ControlContainment
제목
컨테인먼트가 적용된 모듈러 데이터센터의 공조 팬 제어 방안에 관한 실험적 연구
제목 (타언어)
An experimental study on the fan control of computer room air handler in a modular data center with cold-aisle containment
저자
함상우김민휘윤동섭정재원
발행일
2014-10
유형
Proceeding
저널명
대한건축학회 추계학술발표대회논문집
34
2
페이지
285 ~ 286