상암 DMC 지역냉방 냉열사용량 분석에 의한 실제 부하율 예측

Prediction of Actual Load Factors Based on the User Data Analysis of District Cooling in Sangam DMC
  • 류동원
  • 정주현
  • 고명준
  • 허진혁
  • 문승재
  • 외 4명

초록

In order to estimate the capacity increase of cooling plant for the case of saturated occupancy in Sangam DMC, various load factors including diversity factor are analyzed based on the user data during summer season in 2010. The loss rate between supply and demand sides is also evaluated. The most meaningful results include that the predicted diversity factor and loss rate are found to be 0.67 and 0.03, respectively. Further studies, e.g. multi-year data analysis and alternative cooling load-occupancy rate relation, are needed for determining more reasonable load factors.

키워드

Diversity factor(동시부하율)Load factor(부하율)District cooling(지역냉방)
제목
상암 DMC 지역냉방 냉열사용량 분석에 의한 실제 부하율 예측
제목 (타언어)
Prediction of Actual Load Factors Based on the User Data Analysis of District Cooling in Sangam DMC
저자
류동원정주현고명준허진혁문승재이재헌유호선이창준김진배
발행일
2011-07
유형
Proceeding
저널명
대한설비공학회 2011년도 하계학술발표대회 논문집
페이지
539 ~ 544