Practical thermal performance correlations for a wet-coil indirect evaporative cooler

Citations

WEB OF SCIENCE

25
Citations

SCOPUS

26

초록

The objective of this research was to develop practical models for predicting the thermal performance of a wet-coil indirect evaporative cooler (IEC). Through statistical analysis of cooling and heat exchange effectiveness data generated by a simple epsilon-NTU (number of transfer units) method, simplified models returning the thermal performance of a wet-coil IEC were developed. Linear regression equations were derived as a function of the major design parameters and interactions that strongly affected the wet-coil IEC's performance. A pilot wet-coil IEC unit was built to validate the proposed models. Effectiveness data were obtained under a controlled range of operating conditions in an environmental chamber. Then, the energy-saving potential achievable by integrating a wet-coil IEC into a conventional variable air volume (VAV) system for pre-conditioning the outdoor air intake was quantitatively evaluated. The experimental results showed that more than 75% cooling effectiveness and 59% heat reclaim effectiveness could be achieved under wet and dry operating conditions, respectively. The experimental data acquired using the pilot unit agreed well with the thermal effectiveness predicted by the proposed models. Consequently, the VAV system integrated with the wet-coil IEC showed more than 45% reduced annual operating energy consumption compared with the conventional VAV system.

키워드

Evaporative coolingSensible heat exchangerWet-coil indirect evaporative coolerHEAT-EXCHANGERSFLOW
제목
Practical thermal performance correlations for a wet-coil indirect evaporative cooler
저자
Kim, Min-HwiJeong, Duk-SoJeong, Jae-Weon
DOI
10.1016/j.enbuild.2015.03.043
발행일
2015-06
유형
Article
저널명
Energy and Buildings
96
페이지
285 ~ 298