대기온도 변화에 따른 150 MW 화력발전소용 공랭식 복수기 송풍기의 운전수량 선정

Number of Fan in Air Cooled Condenser of a 150 MW Thermal Power Plant with Ambient Air Temperature

초록

During this study, number of fan by ambient air temperature that condenser pressure satisfies steam turbine exhaust pressure condition with intervals of 3℃ within the 150 MW thermal power plant site temperature range of -17.1℃ to 36.7℃ was reviewed. An air cooled condenser changes its operating pressure influenced by cooling air circulation amount by atmospheric temperature and number of fan. For stable power plant operation, these were confirmed to maximize a quantity of air-cooled condenser fans at above or equal from design ambient temperature and to reduce an amount of circulating air to an air cooled condenser by depending on a quantity of fan considering exhaust pressure operation condition of a steam turbine at below design ambient temperature.

키워드

150 MW 석탄화력 발전소공랭식 복수기150 MW thermal power plantair cooled condenser
제목
대기온도 변화에 따른 150 MW 화력발전소용 공랭식 복수기 송풍기의 운전수량 선정
제목 (타언어)
Number of Fan in Air Cooled Condenser of a 150 MW Thermal Power Plant with Ambient Air Temperature
저자
황용훈문승재
발행일
2014-07
유형
Proceeding
저널명
2014 한국플랜트학회 학술대회
2014
1
페이지
165 ~ 169