Field measurement of U-value using multiple sensors at test chamber and EIFS building

Citations

WEB OF SCIENCE

4
Citations

SCOPUS

3

초록

The purpose of this study is to analyse the heat flux difference and examine applicability of the heat flux sensor along with various sensor attachment methods. Using multiple sensors and various tapes, a KS F 2278 thermal test was performed in hot/cold chamber conditions with standard panel specimen. The measured heat flux values of sensors were stable. But values of sensors were smaller than the heat flux result of KS F 2278. Thus, thermal resistance of attachment tape on a sensor should be considered during on site U-value measuring process. This study also examined the differences between measured U-value and design U-value by attaching the different sensors in the same area using multiple heat flux sensors. All cases are shown to the same patterns on each heat flux and U-value graph, but U-values with regard to various sensors have shown some differences to the designed values. Using in-situ measurement, the EIFS wall was found to be difficult to measure accurately due to the small level of heat flux.

키워드

Heat flux sensorU-valueChamber testEIFSEngineeringIndustrial engineeringChamber conditionChamber testsEIFSField measurementHeat flux sensorsIn-situ measurementMultiple sensorsU valuesHeat flux
제목
Field measurement of U-value using multiple sensors at test chamber and EIFS building
저자
No, Sang-TaeJeong, Jae-Weon
DOI
10.1080/13467581.2019.1596810
발행일
2019-03
유형
Article
저널명
Journal of Asian Architecture and Building Engineering
18
2
페이지
63 ~ 71

파일 다운로드