Impact of integrated hot water cooling and desiccant-assisted evaporative cooling systems on energy savings in a data center
- Kim, Min-Hwi;
- Ham, Sang-Woo;
- Park, Jun-Seok;
- Jeong, Jae-Weon
WEB OF SCIENCE
45SCOPUS
49초록
The primary objective of this paper is to propose the integration of a hot water cooling system with a desiccant-assisted evaporative cooling system for air conditioning a data center. The feasibility of the integrated system is analyzed by a detailed energy simulation for a model data center by using TRNSYS (transient system simulation) 16 with a commercial equation solver program. The energy saving potential of the proposed system is evaluated by comparing it to a conventional air handling system with an air-side economizer serving the model data center. The results show that the proposed system saves more than 95% of the peak power demand and 84% of annual operating energy consumption with respect to the conventional air conditioning system for the data center. This advantage in energy savings is primarily obtained by the use of water-side free cooling in the hot water cooling system and the evaporative cooling effect enhanced by the liquid desiccant system in the air-side supply. Fan energy savings caused by reduced air flow in the proposed system also contributes to the reduction in operating energy.
키워드
- 제목
- Impact of integrated hot water cooling and desiccant-assisted evaporative cooling systems on energy savings in a data center
- 저자
- Kim, Min-Hwi; Ham, Sang-Woo; Park, Jun-Seok; Jeong, Jae-Weon
- 발행일
- 2014-12
- 유형
- Article
- 저널명
- Energy
- 권
- 78
- 페이지
- 384 ~ 396