Impact of integrated hot water cooling and desiccant-assisted evaporative cooling systems on energy savings in a data center

Citations

WEB OF SCIENCE

45
Citations

SCOPUS

49

초록

The primary objective of this paper is to propose the integration of a hot water cooling system with a desiccant-assisted evaporative cooling system for air conditioning a data center. The feasibility of the integrated system is analyzed by a detailed energy simulation for a model data center by using TRNSYS (transient system simulation) 16 with a commercial equation solver program. The energy saving potential of the proposed system is evaluated by comparing it to a conventional air handling system with an air-side economizer serving the model data center. The results show that the proposed system saves more than 95% of the peak power demand and 84% of annual operating energy consumption with respect to the conventional air conditioning system for the data center. This advantage in energy savings is primarily obtained by the use of water-side free cooling in the hot water cooling system and the evaporative cooling effect enhanced by the liquid desiccant system in the air-side supply. Fan energy savings caused by reduced air flow in the proposed system also contributes to the reduction in operating energy.

키워드

Data centerHot water coolingLiquid desiccantEvaporative coolingVENTILATION PRECONDITIONING SYSTEMAIR-CONDITIONING SYSTEMLIQUID DESICCANTWASTE HEATPERFORMANCEFEASIBILITYECONOMIZERSELECTRONICSDESIGN
제목
Impact of integrated hot water cooling and desiccant-assisted evaporative cooling systems on energy savings in a data center
저자
Kim, Min-HwiHam, Sang-WooPark, Jun-SeokJeong, Jae-Weon
DOI
10.1016/j.energy.2014.10.023
발행일
2014-12
유형
Article
저널명
Energy
78
페이지
384 ~ 396