공동주택 적용을 위한 액체식 제습 중앙공조시스템의 여름철 현장성능 실증연구

Field Study of a Liquid-Desiccant Central Air-Conditioning System for an Apartment Building
  • 이재희
  • 김보선
  • 추형욱
  • 양지훈
  • 남현민
  • ... 정재원
  • 외 1명

초록

As an alternative to a conventional vapor compression cooling system, a liquid-desiccant central air-conditioning system controlling air temperature and humidity independently, was installed in an apartment building testbed located in Yongin, South Korea. Indoor and supply air conditions of each room were compared, and indoor thermal comfort and energy performance were evaluated under hot and humid weather to verify applicability as a central air-conditioning system for an apartment building. The proposed system can achieve high thermal comfort satisfaction in all rooms, in terms of indoor temperature and humidity distribution and indoor air velocity, when operating for 45 h under the hot and humid weather in summer. The seasonal energy efficiency ratio was estimated to be 1.91, which will increase to 3.40 via the optimization of duct work and the use of energy-efficient fans. Based on the field test results, it can be concluded that the proposed liquid-desiccant system is highly applicable as a central air-conditioning system for multizone apartment buildings.

키워드

중앙 공조시스템에너지 성능현장실증연구실내 열 쾌적성액체식 제습 기술Central Air-Conditioning SystemEnergy performanceField-studyIndoor thermal comfortLiquid-desiccant
제목
공동주택 적용을 위한 액체식 제습 중앙공조시스템의 여름철 현장성능 실증연구
제목 (타언어)
Field Study of a Liquid-Desiccant Central Air-Conditioning System for an Apartment Building
저자
이재희김보선추형욱양지훈남현민이병두정재원
DOI
10.6110/KJACR.2024.36.2.82
발행일
2024-02
저널명
설비공학 논문집
36
2
페이지
82 ~ 90